Communication module SPI – PROFIBUS DP Slave

Communication module SPI – PROFIBUS DP Slave

The comX communication module is designed to be integrated into automation devices to provide drives, robot controllers, PLCs, etc. with a network interface. Communication tasks are all executed autonomously in the module – irrespective of the processor of the target device.

Process data is exchanged via a Dual-Port-Memory per access by an 8-/16-bit bus interface or a fast 50 MHz SPI interface.

comX supports all leading Real-Time Ethernet protocols as Master or Slave and meets all network-specific requirements in just one single module. To support a line topology, the module is equipped with two Ethernet ports. The communication protocol can be changed simply and reliably by loading the appropriate firmware and a software license for masters.

Due to the Hilscher network controller netX, a 10-year delivery guarantee is granted.

  • Universal interface of the PROFIBUS DP Slave with network connector "onboard"
  • Allows a flexible positioning of the network connector
  • Host connection via dual-port memory or SPI
  • Function-compatible substitute for comX 10CA-CCS
ProductPart number1581.420
Brief descriptionCommunication module PROFIBUS Slave
Communication controllernetXnetX 52
Integrated MemoryFLASH4 MB SPI Flash EPROM
Power supply and currentSupply voltage+3.3 V ± 5 % DC
Typical/maximum current 400 mA / 440 mA (at 3.3 V) In case of a short circuit of the 5 V PROFIBUS supply, the current consumption increases by further approx. 70 mA.
Typical power consumption1,35 W
Power connectorvia system bus connector X1
System interfaceTypeParallel or serial dual-port memory interface
Connector50-pin SMT, female connector
Pin distance1.27 mm
Dual-port memory size16 KByte
Data width 8/16 bit
Serial dual-port memory interfaceSPI Slave, mode 3
Baud ratemax. 50 MHz
Communication interfaceCommunication standardPROFIBUS DP Slave
ConnectorRS-485, isolated
Transmission rate (auto detection) 9.6 kBits/s, 19.2 kBits/s, 31.25 kBits/s, 45.45 kBits/s,93.75 kBits/s, 187.5 kBits/s, 500 kBits/s,1.5 MBits/s, 3 MBits/s, 6 MBits/s, 12 MBit/s
Diagnostic interfaceTypeUART or USB
ConnectorSignal at host interface. Available only if integrated in host system.
DisplayLED displaySYS System Status, green: RUN, yellow: RDY
COM communication status, green: RUN, red: ERR
EnvironmentAmbient temperature range for operation-20 °C ... +70 °C (Air flow during measurment: 0,5 m/s)
Ambient temperature range for storage-40 °C … +85 °C
Humidity range10 % … 95 % relative humidity (non-condensing)
DeviceDimensions (L x W x H)70 mm x 30 mm x 21.5 mm
Weightapprox. 35 g ... 40 g
Mountingusing screwable metal bolts, according to comX Design Guide
Configuration Configuration softwareSYCON.net

Omschrijving

Bestelnummer

Communication module SPI - PROFIBUS Slave, COMX 52CA-DPS1581.420/DPS