PROFINET/CAN Gateway Master

With the PN/CAN gateway, the connection of CAN devices to PROFINET is easy and straightforward.

PROFINET/CAN Gateway Master

On the PROFINET network, the PN/CAN gateway is a PROFINET I/O device and supports transfer rates up to 100 Mbps full duplex; and up to 1 Mbps on the CAN bus.
The I/O data of the CAN participants is transparently displayed in a freely configurable manner on the PROFINET network and can thus be processed directly in the PLC. The PN/CAN gateway is integrated with a GSDML file in the hardware configurator and can be fully configured there. No other software tools for configuration or handling blocks for programming are necessary, making gateway use straightforward.
The features of the PN/CAN gateway are rounded out by MRP (media redundancy), as well as extensive diagnostic functions and an interface for online diagnostics.

With the Layer 2 PN/CAN gateway, CAN devices can be connected using proprietary CAN protocols, including devices with the SAE J1939 protocol, among others.

  • Automatic and controlled receive and transmit objects for CAN frames with configurable identifier
  • Transmission objects can also be transmitted cyclically
  • Receive channel FIFO for receiving CAN frames with flexible identifier
  • Transmission channel FIFO for transmitting any CAN frames with flexible identifier
  • Up to 512 different CAN frames configurable
  • Supports CAN 2.0A (11 bit identifier) and CAN 2.0B (29 bit identifier) according to ISO 11898-2
  • Up to 1 Mbit/s CAN bit rate
  • Simple configuration via GSDML file
  • No handling blocks or parameterization software necessary
  • Media redundancy (MRP client)
Dimensions (DxWxH)35 x 84 x 76 mm
Weight Approx. 160 g
PROFINET interface
ProtocolPROFINET IO as defined in IEC 61158-6-10
Physical layerEthernet
Transmission rate100 Mbps
I/O image sizemax. 1440 bytes of input / 1440 bytes of output data
ConnectionRJ45 socket
FeaturesMedia Redundancy Protocol (MRP), automatic addressing / topology detection (LLDP, DCP)
CAN interface
TypeISO/DIN 11898-2 CAN High-speed physical layer
Transmission rate50, 100, 125, 250, 500, 800, 1000 kbps
ProtocolCAN Layer 2 with 11 bit or 29 bit identifier
Connection9-pin D-sub male connector
FeaturesAutomatic and controlled reception and transmission objects, reception channel FIFO, transmission channel FIFO
Status indicator3 LEDs, function status
4 LEDs, Ethernet status
Voltage supply24 V DC, 18–30 V DC
Current drawMax. 250 mA with 24 V DC